Skip to main content
Protection type EN / IEC 61643-11 Τ3 (Class III)
Number of poles 2 + PE
Connection between terminals L–N, L–PE & N – PE or (-ve)–(+ve), (-ve)–PE, +ve)–PE
Installation in AC & DC
Nominal operating voltage, Uo 34 V AC, 48 V DC
Maximum operating voltage, Uc 48 V AC, 60 V DC
Ιsc, “class III” test, (8/20μs), 1P 1,2 kA
Uoc “class III” test, (1,2/50μs), 1P 2,4 kV
Up, (at Ιsc) L-N <500 V
Up, (at Ιsc) L-PE & N-PE <800 V
Responce time, ta, L-N <25 ns
Responce time, ta, L-PE & N-PE <100 ns
Maximum back up fuse 32 A gG
Short circuit withstand, Ιsccr AC 2 kA / 50 Hz
Temporary overvoltage (TOV) 5s 148 V withstand
Thermal protection YES
Monitoring indication Green LED
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 18x90x66 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 4 mm2
Maximum conductor for remote contacts 4 mm2
Conductor terminals tightening torque 1 Nm
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T3 (CAT I)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001

Low voltage SPD PSDC 20/48, code 6801046-70

GTIN:
6801046-80
,
Product code:
6801046-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00