Technical data
Protection type EN / IEC 61643-11 Τ1 (Class I)
Number of poles 4
Connection between terminals L1–N, L2–N, L3–N & N–PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 300 V (L–N) / 305 V (N–PE), 50 Hz
Ιimp, “class I” test, (10/350μs), 1P 25 kA (L–N) / 100 kA (N–PE)
Ιmax, “class II” test, (8/20μs), 1P 65 kA (L–N) / 130 kA (N–PE)
Ιn, “class II” test, (8/20μs), 1P 25 kA (L–N) / 100 kA (N–PE)
Up, (at In) <1,5 kV (L–N) / <1,5 kV (N–PE)
Responce time, ta <25 ns (L–N) / <100 ns (N–PE)
Maximum back up fuse <315 A gG
Short circuit withstand, Ιsccr 50 kA / 50 Hz
Follow current interrupt rating (N–PE), Ifi 100 A rms
Temporary overvoltage (TOV) 120min L-N 442 V withstand
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 144x106x87 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T1 (CAT IV) + T2 (CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Four poles SPD T1 (class I), in 3+1 wiring (3P + N) suitable for installation in TT, TN S &amp; TN CS systems. It is equipped with 3 protection modules of innovative design (protect...
GTIN:
6825425-80
,
Product code:
6825425-70
,
Customs tariff No.:,
Gross weight:
427.00
,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ1 (Class I)
Number of poles 4
Connection between terminals L1–N, L2–N, L3–N & N–PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 300 V (L–N) / 305 V (N–PE), 50 Hz
Ιimp, “class I” test, (10/350μs), 1P 12,5 kA (L–N) / 50 kA (N–PE)
Ιmax, “class II” test, (8/20μs), 1P 65 kA (L–N) / 100 kA (N–PE)
Ιn, “class II” test, (8/20μs), 1P 20 kA (L–N) / 50 kA (N–PE)
Up, (at In) <1,5 kV (L–N) / <1,5 kV (N–PE)
Responce time, ta <25 ns (L–N) / <100 ns (N–PE)
Maximum back up fuse <315 A gG
Short circuit withstand, Ιsccr 25 kA / 50 Hz
Follow current interrupt rating (N–PE), Ifi 100 A rms
Temporary overvoltage (TOV) 120min L-N 442 V withstand
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 72x106x87 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T1 (CAT IV) + T2 (CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Four poles SPD T1 (class I), in 3+1 wiring (3P + N) suitable for installation in TT, TN S &amp; TN CS systems. It is equipped with 3 protection modules of innovative design (protect...
GTIN:
6825412-80
,
Product code:
6825412-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ1 (Class I)
Number of poles 1
Connection between terminals L–N, L-PEN
Installation in TN S, TN CS, TN C, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 300 V, 50 Hz
Ιimp, “class I” test, (10/350μs), 1P 12,5 kA
Ιmax, “class II” test, (8/20μs), 1P 65 kA
Ιn, “class II” test, (8/20μs), 1P 20 kA
Up, (at In) <1,5 kV
Responce time, ta <25 ns
Maximum back up fuse <315 A gG
Short circuit withstand, Ιsccr 25 kA / 50 Hz
Temporary overvoltage (TOV) 120min L-N 442 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 17,5x106x87 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T1 (CAT IV) + T2 (CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Single pole SPD T1 (class I), for connection between L–N &amp; L–PEN, suitable for installation in TT, TN S, TN CS &amp; TN C systems. It is equipped with 1 protection module of inn...
GTIN:
6825112-80
,
Product code:
6825112-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ1 (Class I)
Number of poles 1
Connection between terminals N-PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 305 V, 50 Hz
Ιimp, “class I” test, (10/350μs), 1P 50 kA
Ιmax, “class II” test, (8/20μs), 1P 100 kA
Ιn, “class II” test, (8/20μs), 1P 50 kA
Up, (at In) <1,5 kV
Responce time, ta <100 ns
Follow current interrupt rating, Ifi 100 A rms
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 17,5x106x87 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T1 (CAT IV) + T2 (CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Single pole SPD T1 (class I), equipped with a heavy duty spark gap sealed into a noble gas filled cylinder. It is intended to be connected between N–PE and is suitable for installat...
GTIN:
6825050-80
,
Product code:
6825050-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ1 (Class I)
Number of poles 4
Connection between terminals L1–N, L2–N, L3–N & N–PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 320 V (L–N) / 255 V (N–PE), 50 Hz
Ιimp, “class I” test, (10/350μs), 1P 12,5 kA (L–N) / 50 kA (N–PE)
Ιmax, “class II” test, (8/20μs), 1P 50 kA (L–N) / 50 kA (N–PE)
Ιn, “class II” test, (8/20μs), 1P 20 kA (L–N) / 20 kA (N–PE)
Up, (at In) <1,5 kV (L–N) / <1,5 kV (N–PE)
Responce time, ta <25 ns (L–N) / <100 ns (N–PE)
Maximum back up fuse <250 A gG
Short circuit withstand, Ιsccr 25 kA / 50 Hz
Follow current interrupt rating (N–PE), Ifi 100 A rms
Temporary overvoltage (TOV) 120min L-N 440 V fail safe
Temporary overvoltage (TOV) 5s L-N 352 V withstand
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 72x99x71 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T1 (CAT IV) + T2 (CAT III & CAT II) + T3 CAT I)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Four poles SPD T1 (class I), in 3+1 wiring (3P + N) suitable for installation in TT, TN S &amp; TN CS systems. It is equipped with 3 protection modules of innovative design (protect...
GTIN:
6844491-80
,
Product code:
6844491-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ1 (Class I)
Number of poles 2
Connection between terminals L1–N, N–PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 320 V (L–N) / 255 V (N–PE), 50 Hz
Ιimp, “class I” test, (10/350μs), 1P 12,5 kA (L–N) / 50 kA (N–PE)
Ιmax, “class II” test, (8/20μs), 1P 50 kA (L–N) / 50 kA (N–PE)
Ιn, “class II” test, (8/20μs), 1P 20 kA (L–N) / 20 kA (N–PE)
Up, (at In) <1,5 kV (L–N) / <1,5 kV (N–PE)
Responce time, ta <25 ns (L–N) / <100 ns (N–PE)
Maximum back up fuse <250 A gG
Short circuit withstand, Ιsccr 25 kA / 50 Hz
Follow current interrupt rating (N–PE), Ifi 100 A rms
Temporary overvoltage (TOV) 120min L-N 440 V fail safe
Temporary overvoltage (TOV) 5s L-N 352 V withstand
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 36x99x71 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T1 (CAT IV) + T2 (CAT III & CAT II) + T3 CAT I)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Two poles SPD T1 (class I), in 1+1 wiring (P + N) suitable for installation in TT, TN S &amp; TN CS systems. It is equipped with a heavy duty varistor (protection between phase–neut...
GTIN:
6844291-80
,
Product code:
6844291-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ2 (Class II)
Number of poles 4
Connection between terminals L1–N, L2–N, L3–N & N–PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 300 V (L–N) / 305 V (N–PE), 50 Hz
Ιmax, “class II” test, (8/20μs), 1P 50 kA (L–N) / 65 kA (N–PE)
Ιn, “class II” test, (8/20μs), 1P 20 kA (L–N) / 40 kA (N–PE)
Up, (at In) <1,5 kV (L–N) / <1,5 kV (N–PE)
Responce time, ta <25 ns (L–N) / <100 ns (N–PE)
Maximum back up fuse <315 A gG
Short circuit withstand, Ιsccr 25 kA / 50 Hz
Follow current interrupt rating (N–PE), Ifi 100 A rms
Temporary overvoltage (TOV) 120min L-N 442 V withstand
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 72x105x70 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T2 (CAT IV CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Four poles SPD T2 (class II), in 3+1 wiring (3P + N) suitable for installation in TT, TN S &amp; TN CS systems. It is equipped with 3 protection modules of innovative design (protec...
GTIN:
6854150-80
,
Product code:
6854150-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ2 (Class II)
Number of poles 1
Connection between terminals L–N, L–PEN
Installation in TN S, TN CS, TN C, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 300 V (L–N), 50 Hz
Ιmax, “class II” test, (8/20μs), 1P 50 kA
Ιn, “class II” test, (8/20μs), 1P 20 kA
Up, (at In) <1,5 kV
Responce time, ta <25 ns
Maximum back up fuse <315 A gG
Short circuit withstand, Ιsccr 25 kA / 50 Hz
Temporary overvoltage (TOV) 120min L-N 442 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 17,5x106x70 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T2 (CAT IV CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Single pole SPD T2 (class II), for connection between L–N &amp; L–PEN, suitable for installation in TT, TN S, TN CS &amp; TN C systems. It is equipped with 1 protection module of in...
GTIN:
6850150-80
,
Product code:
6850150-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ2 (Class II)
Number of poles 1
Connection between terminals L–N, L–PEN
Installation in TN S, TN CS, TN C, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 350 V (L–N), 50 Hz
Ιmax, “class II” test, (8/20μs), 1P 50 kA
Ιn, “class II” test, (8/20μs), 1P 20 kA
Up, (at In) <1,75 kV
Responce time, ta <25 ns
Maximum back up fuse <315 A gG
Short circuit withstand, Ιsccr 25 kA / 50 Hz
Temporary overvoltage (TOV) 120min L-N 440 V fail safe
Temporary overvoltage (TOV) 5s L-N 403 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <100 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 17,5x106x70 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts No remote contacts
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T2 (CAT IV CAT III & CAT II)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Single pole SPD T2 (class II), for connection between L–N &amp; L–PEN, suitable for installation in TT, TN S, TN CS &amp; TN C systems. It is equipped with 1 protection module of in...
GTIN:
6840150-80
,
Product code:
6840150-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-11 Τ2 (Class II)
Number of poles 1
Connection between terminals N–PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 305 V (N–PE), 50 Hz
Ιmax, “class II” test, (8/20μs), 1P 65 kA
Ιn, “class II” test, (8/20μs), 1P 40 kA
Up, (at In) <1,5 kV
Responce time, ta <100 ns
Follow current interrupt rating (N–PE), Ifi 100 A rms
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Thermal protection & monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 17,5x106x70 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T2 (CAT IV CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Single pole SPD T2 (class II), equipped with a spark gap sealed into a noble gas filled cylinder. It is intended to be connected between N–PE and is suitable for installation in TT,...
GTIN:
6850151-80
,
Product code:
6850151-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00