Skip to main content
Protection type EN / IEC 61643-11 Τ2 (Class II)
Number of poles 2
Connection between terminals L–N, N–PE
Installation in TN S, TN CS, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 300 V (L–N) / 305 V (N–PE), 50 Hz
Ιmax, “class II” test, (8/20μs), 1P 50 kA (L–N) / 65 kA (N–PE)
Ιn, “class II” test, (8/20μs), 1P 20 kA (L–N) / 40 kA (N–PE)
Up, (at In) <1,5 kV (L–N) / <1,5 kV (N–PE)
Responce time, ta <25 ns (L–N) / <100 ns (N–PE)
Maximum back up fuse <315 A gG (@ Isccr 25 kA) / <250 A gG (@ Isccr 50 kA)
Short circuit withstand, Ιsccr 25 kA (@ 315 A fuse gG) /50 kA (@250 A fuse gG)
Follow current interrupt rating (N–PE), Ifi 100 A rms
Temporary overvoltage (TOV) 120min L-N 440 V fail safe
Temporary overvoltage (TOV) 5s L-N 335 V withstand
Temporary overvoltage (TOV) 200ms N-PE 1200 V withstand
Monitoring indication YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 36x90x78 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Combined equivalent protection as per EN / IEC 61643-11 T2 (CAT III & CAT II) + T3 CAT I)
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001

SPD T2 M spec 300 1+1, code 6832303-70

H.S Code:
853663090
,
Product code:
6832303-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00