Fasteners for lightning protection conductors

Conductor fasteners

Fasteners used in air termination and down conductors in a Lightning Protection System (LPS) tested according to IEC ΕΝ 62561 - 4 

Technical data
Material Conductor fastener: stainless steel (SSt – grade V2A). Spacer: plastic (PL).
Screws M6x16 mm, V2A stainless steel screws. One stainless steel wood fixing screw.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Al, Cu, Cu/eSn, SSt (Stainless Steel), St/eCu, St/tZn
Tightening torque of conductor 3,5Nm.
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. ≤1000 mm for stranded conductor used for heights ≤20 m. ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
H.S Code:
6161101-71
,
Product code:
6161101-71
,
Customs tariff No.:,
Gross weight:
52.00
gr,
PU:
Technical data
Material Copper (Cu).
Screws M6x16 mm, V2A stainless steel screws. One stainless steel wood fixing screw.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Up to 40x6 mm
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel)
Tightening torque of conductor 3,5Nm.
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤500 mm1).
Spacing between fasteners of down conductors ≤1000 mm for heights ≤20 m. ≤500 mm for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening tape conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
H.S Code:
6121240-71
,
Product code:
6121240-71
,
Customs tariff No.:,
Gross weight:
92.00
gr,
PU:
Technical data
Material Clamp for pipe or rounded end: Aluminium alloy. Conductor fastener: Hot dip galvanized steel.
Screws M6x16 mm, V2A stainless steel screws. M6x25 mm, V2A stainless steel carriage bolt, nut & washer.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Ø8–10 mm (50–70 mm2).
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn.
Tightening torque of conductor 3,5Nm.
Diameter of pipe or rounded end Ø12–24 mm
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. ≤1000 mm for stranded conductor used for heights ≤20 m. ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor used in air termination system, down conductor system. Suitable for roofs with round horizontal seam, pipes or rounded ends.
H.S Code:
6104024-71
,
Product code:
6104024-71
,
Customs tariff No.:,
Gross weight:
112.00
gr,
PU:
Technical data
Material Fastener: Hot dip galvanized steel (St/tZn). Spacer: Aluminium.
Screws M6x16 mm, V2A stainless steel screws.
Spacer's height 50 mm.
Spacer's inner thread M8.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Ø8–10 mm (50–70 mm2).
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn.
Tightening torque of conductor 3,5Nm.
Fixing on brick or concrete Through a head threaded drive pin (not included) and a PVC wall plug (not included).
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. ≤1000 mm for stranded conductor used for heights ≤20 m. ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete.
H.S Code:
6102158-71
,
Product code:
6102158-71
,
Customs tariff No.:,
Gross weight:
76.00
gr,
PU:
Technical data
Material Fastener: Hot dip galvanized steel (St/tZn). Spacer: Aluminium.
Screws M6x16 mm, V2A stainless steel screws.
Spacer's height 50 mm.
Spacer's inner thread M6.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Ø8–10 mm (50–70 mm2).
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn.
Tightening torque of conductor 3,5Nm.
Fixing on brick or concrete Through a head threaded drive pin (not included) and a PVC wall plug (not included).
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. ≤1000 mm for stranded conductor used for heights ≤20 m. ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete.
H.S Code:
6102156-71
,
Product code:
6102156-71
,
Customs tariff No.:,
Gross weight:
73.00
gr,
PU:
Technical data
Material Fastener: Hot dip galvanized steel (St/tZn). Spacer: Aluminium.
Screws M6x16 mm, V2A stainless steel screws
Spacer's height 20 mm
Spacer's inner thread M8
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn
Tightening torque of conductor 3,5Nm
Fixing on brick or concrete Through a head threaded drive pin (not included) and a PVC wall plug (not included)
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. ≤1000 mm for stranded conductor used for heights ≤20 m. ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete.
H.S Code:
6102108-71
,
Product code:
6102108-71
,
Customs tariff No.:,
Gross weight:
60.00
gr,
PU:
50.00
Technical data
Material Fastener: Copper (Cu).
Screws M6x16 mm, V2A stainless steel screws. One stainless steel wood fixing screw.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Up to 30x6 mm.
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel)
Tightening torque of conductor 3,5 Nm.
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤500 mm1).
Spacing between fasteners of down conductors ≤1000 mm for heights ≤20 m. ≤500 mm for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening tape conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
H.S Code:
6121202-71
,
Product code:
6121202-71
,
Customs tariff No.:,
Gross weight:
70.00
gr,
PU:
50.00
Technical data
Material Hot dip galvanized steel (St/tZn).
Screws M6x16 mm, V2A stainless steel screws. One electroplated zinc steel wood fixing screw.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Up to 40x6 mm.
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn.
Tightening torque of conductor 3,5Nm.
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included).
Spacing between fasteners of air termination conductors ≤500 mm1).
Spacing between fasteners of down conductors ≤1000 mm for heights ≤20 m. ≤500 mm for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component ≤300 mm.
Fastening tape conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
H.S Code:
6101240-71
,
Product code:
6101240-71
,
Customs tariff No.:,
Gross weight:
88.00
gr,
PU:
50.00
Technical data
Material Fastener: Hot dip galvanized steel (St/tZn). Spacer: Aluminium.
Screws M6x16 mm, V2A stainless steel screws
Spacer's height 20 mm
Spacer's inner thread Μ6
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn
Tightening torque of conductor 3,5 Nm
Fixing on brick or concrete Through a head threaded drive pin (not included) and a PVC wall plug (not included).
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. ≤1000 mm for stranded conductor used for heights ≤20 m. ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete.
H.S Code:
6102106-71
,
Product code:
6102106-71
,
Customs tariff No.:,
Gross weight:
50.00
gr,
PU:
50.00
Technical data
Material Copper (Cu)
Screws M6x16 mm, V2A stainless steel screws. One stainless steel wood fixing screw.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N. Axial load, 50 N.
Conductor's dimensions Ø6 mm (25–35 mm2)
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel), St/eCu
Tightening torque of conductor 3,5 Nm
Fixing on brick or concrete wall Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included).
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. ≤1000 mm for stranded conductor used for heights ≤20 m. ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.