Fasteners for lightning protection conductors

Conductor fasteners

Fasteners used in air termination and down conductors in a Lightning Protection System (LPS) tested according to IEC ΕΝ 62561 - 4 

Technical data
Material Copper (Cu)
Screws M6x16 mm, V2A stainless steel screws, one stainless steel wood fixing screw
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel), St/eCu
Tightening torque of conductor 3,5Nm
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). / ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. / ≤1000 mm for stranded conductor used for heights ≤20 m. / ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
GTIN:
6121100-81
,
Product code:
6121100-71
,
Customs tariff No.:
929.3.1.8
,
Gross weight:
68.00
,
PU:
50.00
Technical data
Material Conductor fastener: copper (Cu) / Spacer: plastic (PL)
Screws M6x16 mm, V2A stainless steel screws, one stainless steel wood fixing screw
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel), St/eCu
Tightening torque of conductor 3,5Nm
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). / ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. / ≤1000 mm for stranded conductor used for heights ≤20 m. / ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
GTIN:
6121102-81
,
Product code:
6121102-71
,
Customs tariff No.:,
Gross weight:
56.00
,
PU:
50.00
Technical data
Material Copper (Cu) fastener, polyamid support, PVC expansion plug for the fixation.
Screws M6x16 mm, V2A stainless steel screws, one stainless steel cross recessed countersunk screw M5x80 mm
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel), St/eCu
Tightening torque of conductor 3,5Nm
Fixing For the installation is needed a Ø12 mm hole on the tile (not with impact driver). The fixation of the fastener and the sealing of the hole is achieved through the M5x80 mm screw and nut which are compressing the PVC expansion plug to the hole.
Spacing between fasteners (Where additional mechanical strength is required, e.g snow, strong winds etc, the spacing between the fasteners should be ≤300 mm.) ≤1000 mm for solid conductor. / ≤500 mm for stranded conductor. / ≤300 mm before and after of change of direction or clamp or contraction-expansion absorbing component.
Fastening round or stranded conductor used in air termination system. Suitable for tile roofs.
GTIN:
6122121-81
,
Product code:
6122121-71
,
Customs tariff No.:
929.3.1.7
,
Gross weight:
72.00
,
PU:
25.00
Technical data
Material Fastener: Copper (Cu). / Spacer: Copper alloy (Cu-A). / Base: Stainless steel (SSt).
Screws M6x16 mm, V2A stainless steel screws.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel), St/eCu
Tightening torque of conductor 3,5Nm
Fixing On the fixing screws of the roof panel.
Spacing between fasteners (Where additional mechanical strength is required, e.g snow, strong winds etc, the spacing between the fasteners should be ≤300 mm.) ≤1000 mm for solid conductor. / ≤500 mm for stranded conductor. / ≤300 mm before and after of change of direction or clamp or contraction-expansion absorbing component.
Fastening round or stranded conductor used in air termination system. Suitable for eternite roofs or corrugated metal roofs.
GTIN:
6122102-81
,
Product code:
6122102-71
,
Customs tariff No.:,
Gross weight:
78.00
,
PU:
50.00
Technical data
Material Copper (Cu)
Screws M6x16 mm, V2A stainless steel screws, one stainless steel wood fixing screw
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø16 mm
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel)
Tightening torque of conductor 3,5Nm
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners ≤1000 mm
Fastening round rod. Used in air termination rods, down conductor system (earth lead-in rods). Suitable for brick or concrete walls.
GTIN:
6121300-81
,
Product code:
6121300-71
,
Customs tariff No.:,
Gross weight:
85.00
,
PU:
50.00
Technical data
Material Copper (Cu)
Screws M6x16 mm, V2A stainless steel screws, one stainless steel wood fixing screw
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Up to 30x6 mm
Compatibility with conductors made of Cu, Cu/eSn, SSt (Stainless Steel)
Tightening torque of conductor 3,5Nm
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤500 mm1).
Spacing between fasteners of down conductors ≤1000 mm for heights ≤20 m. / ≤500 mm for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening tape conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
GTIN:
6121200-81
,
Product code:
6121200-71
,
Customs tariff No.:,
Gross weight:
80.00
,
PU:
50.00
Technical data
Material Hot dip galvanized steel (St/tZn)
Screws M6x14 mm, V2A stainless steel screws, one electroplated zinc steel wood fixing screw
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn
Tightening torque of conductor 2,5Nm
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). / ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. / ≤1000 mm for stranded conductor used for heights ≤20 m. / ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
GTIN:
6101100-81
,
Product code:
6101100-71
,
Customs tariff No.:
929.3.1.2
,
Gross weight:
62.00
,
PU:
50.00
Technical data
Material Conductor fastener: hot dip galvanized steel (St/tZn) / Spacer: plastic (PL)
Screws M6x14 mm, V2A stainless steel screws, one electroplated zinc steel wood fixing screw
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn
Tightening torque of conductor 2,5Nm
Fixing on brick or concrete Through a wood fixing screw (included) and a PVC wall plug Ø8 mm (not included)
Spacing between fasteners of air termination conductors ≤1000 mm for solid conductor1). / ≤500 mm for stranded conductor1).
Spacing between fasteners of down conductors ≤1000 mm for solid conductor. / ≤1000 mm for stranded conductor used for heights ≤20 m. / ≤500 mm for stranded conductor for heights ≥20 m.
Before and after of change of direction or clamp or contraction-expansion absorbing component. ≤300 mm.
Fastening round or stranded conductor. Used in air termination system, down conductor system. Suitable for brick or concrete surfaces.
GTIN:
6101102-81
,
Product code:
6101102-71
,
Customs tariff No.:,
Gross weight:
56.00
,
PU:
50.00
Technical data
Material Hot dip galvanized steel (St/tZn) fastener, polyamid support, PVC expansion plug for the fixation.
Screws M6x16 mm, V2A stainless steel screws, one St/eZn cross recessed countersunk screw M5x80 mm.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn
Tightening torque of conductor 3,5Nm
Fixing For the installation is needed a Ø12 mm hole on the tile (not with impact driver). The fixation of the fastener and the sealing of the hole is achieved through the M5x80 mm screw and nut which are compressing the PVC expansion plug to the hole.
Spacing between fasteners (Where additional mechanical strength is required, e.g snow, strong winds etc, the spacing between the fasteners should be ≤300 mm.) ≤1000 mm for solid conductor. / ≤500 mm for stranded conductor. / ≤300 mm before and after of change of direction or clamp or contraction-expansion absorbing component.
Fastening round or stranded conductor used in air termination system. Suitable for tile roofs.
GTIN:
6102121-81
,
Product code:
6102121-71
,
Customs tariff No.:
929.3.1.1
,
Gross weight:
70.00
,
PU:
25.00
Technical data
Material Fastener: Hot dip galvanized steel (St/tZn). / Spacer: Aluminium (Al). / Base: Stainless steel (SSt).
Screws M6x16 mm, V2A stainless steel screws.
Withstands (according to IEC ΕΝ 62561-4) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø8–10 mm (50–70 mm2)
Compatibility with conductors made of Al, SSt (Stainless Steel), St/tZn
Tightening torque of conductor 3,5Nm
Fixing On the fixing screws of the roof panel.
Spacing between fasteners (Where additional mechanical strength is required, e.g snow, strong winds etc, the spacing between the fasteners should be ≤300 mm.) ≤1000 mm for solid conductor. / ≤500 mm for stranded conductor. / ≤300 mm before and after of change of direction or clamp or contraction-expansion absorbing component.
Fastening round or stranded conductor used in air termination system. Suitable for eternite roofs or corrugated metal roofs.
GTIN:
6102102-81
,
Product code:
6102102-71
,
Customs tariff No.:,
Gross weight:
62.00
,
PU:
50.00