Skip to main content
Protection type EN / IEC 62561-3 H
DC sparkover voltage at 100V/s 500 V ± 20%
AC sparkover voltage at 50Hz 350 V ± 20%
Typical impulse sparkover voltage at 1kV/μs 950V
Max impulse sparkover voltage at 1kV/μs 1300V
Lightning current discharge 10/350μs, Iimp 3x100 kA (Class H)
DC follow current after the Iimp 200 A / 0,5 s
Surge current discharge 8/20μs 10x100 kA
High energy surge current discharge 10/45μs 20x 60 kA
AC current discharge 50Hz, t=1s 5x100 Arms
AC current discharge 50Hz, t=0,5s 1x200 Arms
AC current discharge 50Hz, t=0,25s 1x4000 Arms
Follow current extinguish capability At 230 V < 20 Arms
Insulation resistance at 100V DC 1 GΩ
Capacitance at 1kHz 7 pF
Dimensions (Diameter / length) 60 x 150 mm
Mounding connections M8 Thread
Tightening torque 13 Nm
Protection level of housing ΙΡ67
Operating temperature -40 oC ÷ +80 oC
Relative humidity 10% ÷ 95%
Housing material Ceramic, EPOXY
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001

Isolation spark gap ISG H, code 6601103-70

GTIN:
6601103-80
,
Product code:
6601103-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00