Skip to main content
Protection type EN / IEC 61643-11 Τ2 (Class II)
Number of poles 3
Connection between terminals -ve ÷ +ve / -ve ÷ PE / +ve ÷ PE
Nominal operating voltage, Un Up to 1500 V DC
Maximum operating voltage, Uc 1500 V DC
Ιmax, “class II” test, (8/20μs), 1P 30 kA
Ιn, “class II” test, (8/20μs), 1P 20 kA
Up, (at In) <5 kV
Responce time, ta <25 ns
Maximum back up fuse Not required for up to 11 kADC expected short circuit current
Short circuit withstand, Ιscpv 11 kA
Thermal protection & monitoring indication YES
Residual current, IPE <100 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 54x95x70 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Housing material Polycarbonate halogen free
Maximum conductor for terminal 35 mm2
Conductor terminals tightening torque 2,5 Nm
Maximum conductor for remote contacts 1,5 mm2
Certification VDE, CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001

SPD PVTron T2 1500 Y RC, code 6852316-70

GTIN:
6852316-80
,
Product code:
6852316-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00