Skip to main content
Material Galvanized steel.
Screws M5x20 mm, galvanized steel screws for conductor fixing. M8x50 mm galvanized steel head threaded drive pin for surface fixing.
Withstands (according to IEC TS 62561-8) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø25.
Tightening torque of conductor 2 Nm
Fixing on brick or concrete Through the head threaded drive pin (included) and a PVC wall plug (not included).
Spacing between fasteners of air termination conductors ≤1000 mm or ≤300 mm before and after of change of direction (where additional mechanical strength is required, e.g snow, strong winds etc, the spacing between the fasteners may be reduced).

Fastener for Lightning Current Control Cable (LCCC) insulating down conductor, code 6104810-71

GTIN:
6104810-81
,
Product code:
6104810-71
,
Customs tariff No.:,
Gross weight: ,
PU: