Isolated LPS

Isolated LPS

An isolated lightning protection system (isolated LPS), can be intalled on the building or beside the equipment to be protected, but at all cases it should keep the required safety distance from the metal installations, as it is defined by the standard IEC EN 62305 - 3. The components used for isolated LPS systems are tested according to IEC TC 62561 - 8. 

Technical data
Outer diameter 25 mm.
Cross sectional area 50 mm2.
Core material Aluminium (Al).
Semiconducting layer- YES
Insulation withstanding 1 MV
Equivalent separation distance for air (se) 95 cm.
Installation Above ground.
Insulating conductor used in isolated lightning protection systems, as down conductor, with the purpose to reduce the separation distance.
GTIN:
6448050-80
,
Product code:
6448050-70
,
Customs tariff No.:,
Gross weight: ,
PU:
Technical data
Diameter 15 mm.
Length 600 mm.
Material Aluminium (Al).
Electrical resistivity <0,036 μΩm
Tensile strength 120 – 280 N/mm2
Installation location Outdoor.
Can be connected with Al, Stainless Steel (SSt), St/tZn.
Connection arrangements Cross (B1). / “T” (B4).
Dimensions of round conductor to be connected Ø8–10mm (50–70 mm2).
Dimensions of tape conductor to be connected Up to 5 mm thickness.
Tightening torque 20 Nm.
Aluminium rod used as air termination rod.
GTIN:
6441206-80
,
Product code:
6441206-70
,
Customs tariff No.:,
Gross weight:
358.00
,
PU:
1.00
Technical data
Diameter 15 mm.
Length 300 mm.
Material Aluminium (Al).
Electrical resistivity <0,036 μΩm
Tensile strength 120 – 280 N/mm2
Installation location Outdoor.
Can be connected with Al, Stainless Steel (SSt), St/tZn.
Connection arrangements Cross (B1). / “T” (B4).
Dimensions of round conductor to be connected Ø8–10mm (50–70 mm2).
Dimensions of tape conductor to be connected Up to 5 mm thickness.
Tightening torque 20 Nm.
Aluminium rod used as air termination rod.
GTIN:
6441203-80
,
Product code:
6441203-70
,
Customs tariff No.:,
Gross weight:
192.00
,
PU:
1.00
Technical data
Material Acetal.
Shape Tube.
Dimensions Ø50x1000 mm with both ends internal threaded.
Wall thickness 15 mm.
Effective length, leff 1000 mm.
Connection to air termination rod Through aluminium connection point with M8 thread at the top, for the air termination rod connection through suitable dowel.
Connection to mast Through internal thread at the bottom of the insulator.
Can be connected with Al, Cu, Copper Alloy ( Cu–A), Cu/eNi, Cu/eSn, Stainless Steel (SSt), St/tZn.
Mast insulator for supporting air termination rod Ø15x300 mm or Ø15x600 mm on metallic mast.
GTIN:
6070002-71
,
Product code:
6070002-71
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Material Aluminium (Al).
Bolts / nuts M8x16 mm, V2A stainless steel hex socket set screws.
Connection to LCCC insulating down conductor (ELEMKO code 64 48 050). / Clamp for Ø10 mm conductor.
Connection arrangement Cross (B1). / Parallel (B2).
Installation Above ground.
Can be connected with Al, Stainless Steel (SSt), St/tZn.
Tightening torque 10 Nm (use additionally threadlocker).
Termination, for connecting the LCCC insulating down conductor (ELEMKO code 64 48 050) to the Lightning Protection System.
GTIN:
6540002-81
,
Product code:
6540002-71
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Material Aluminium (Al).
Bolts / nuts M8x16 mm, V2A stainless steel hex socket set screws.
Connection to LCCC insulating down conductor (ELEMKO code 64 48 050). / Air termination rod with reception for Ø10 mm conductor.
Connection arrangement Parallel connection (B2).
Installation Above ground.
Can be connected with Al, Stainless Steel (SSt), St/tZn.
Tightening torque 10 Nm (use additionally threadlocker).
Termination, for connecting the LCCC insulating down conductor (ELEMKO code 64 48 050) to air termination rod.
GTIN:
6540001-81
,
Product code:
6540001-71
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00
Technical data
Material Galvanized steel.
Screws M5x20 mm, galvanized steel screws for conductor fixing. M8x50 mm galvanized steel head threaded drive pin for surface fixing.
Withstands (according to IEC TS 62561-8) Lateral load, 200 N / Axial load, 50 N
Conductor's dimensions Ø25.
Tightening torque of conductor 2 Nm
Fixing on brick or concrete Through the head threaded drive pin (included) and a PVC wall plug (not included).
Spacing between fasteners of air termination conductors ≤1000 mm or ≤300 mm before and after of change of direction (where additional mechanical strength is required, e.g snow, strong winds etc, the spacing between the fasteners may be reduced).
Fastening insulating conductor in isolated lightning protection systems. Suitable for brick or concrete surfaces.