Skip to main content
Protection type EN / IEC 61643-11 Τ3 (Class III)
Number of poles 3
Connection between terminals L–N, N–PE
Installation in TN S, TN CS, TN C, TT
Nominal operating voltage, Un 230/400 V, 50 Hz
Maximum operating voltage, Uc 275 V (L–N) / 255 V (N–PE), 50 Hz
Ιsc, “class III” test, (8/20μs), 1P 3 kA (L–N, N–PE) / 5 kA (L+N / PE)
Uoc “class III” test, (1,2/50μs), 1P 6 kV (L–N, N–PE) / 10 kV (L+N / PE)
Up, (at Ιsc) <1,5 kV (L–N) / <1,5 kV (N–PE)
Responce time, ta <25 ns (L–N) / <100 ns (N–PE)
Maximum back up fuse 16 A MCB Type B + 30 mA RCD type A
Short circuit withstand, Ιsccr 1 kA / 50 Hz
Temporary overvoltage (TOV) 120min L-N 442 V fail safe
Temporary overvoltage (TOV) 5s L-N 337 V withstand
Temporary overvoltage (TOV) 200ms N-PE 1200 V fail safe
Thermal protection YES
Residual current, IPE <5 μA
Installation location indoor
Protection level of housing ΙΡ20 (built in)
Dimensions WxHxD (mm) 35x25x12 mm
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Connection conductors 3 built-in, 1 mm2 cross sectional area, 114 mm length of colors brown, blue and green/yellow
Housing material Polycarbonate halogen free
Status indication Buzzer in case of failure
Combined equivalent protection as per TS 61643–12 & IEC 61643-12 T3 (CAT I)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001

SPD Mini T3, code 6825305-70

GTIN:
6825305-80
,
Product code:
6825305-70
,
Customs tariff No.:,
Gross weight: ,
PU:
1.00