Skip to main content

SPDs for telecom and signaling

Telecom SPDs
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 1 + shield
Connection between terminals L1–L2, L1–GND, L2–GND
Maximum operating voltage, Uc 64 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 160 V
Up, C3 (at 1 kV), L-L & L-GND < 84 V
Up, C3 (at 1 kV), shield - GND < 276 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to 1 ...
GTIN:
6845122-80
,
Product code:
6845122-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 1 + shield
Connection between terminals L1–L2, L1–GND, L2–GND
Maximum operating voltage, Uc 52 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 140 V
Up, C3 (at 1 kV), L-L & L-GND < 69 V
Up, C3 (at 1 kV), shield - GND < 276 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to 1 ...
GTIN:
6845121-80
,
Product code:
6845121-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 1 + shield
Connection between terminals L1–L2, L1–GND, L2–GND
Maximum operating voltage, Uc 28 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 70 V
Up, C3 (at 1 kV), L-L & L-GND < 37 V
Up, C3 (at 1 kV), shield - GND < 276 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to 1 ...
GTIN:
6845124-80
,
Product code:
6845124-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 1 + shield
Connection between terminals L1–L2, L1–GND, L2–GND
Maximum operating voltage, Uc 15 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 42 V
Up, C3 (at 1 kV), L-L & L-GND < 21 V
Up, C3 (at 1 kV), shield - GND < 276 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to 1 ...
GTIN:
6845120-80
,
Product code:
6845120-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 2
Connection between terminals L1–L2, L1–GND, L2–GND, L3–L4, L3–GND, L4–GND
Maximum operating voltage, Uc 64 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιimp, D1 test, (10/350μs), 4P 5 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 160 V
Up, C3 (at 1 kV), L-L & L-GND < 84 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to up...
GTIN:
6844128-80
,
Product code:
6844128-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 2
Connection between terminals L1–L2, L1–GND, L2–GND, L3–L4, L3–GND, L4–GND
Maximum operating voltage, Uc 52 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιimp, D1 test, (10/350μs), 4P 5 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 140 V
Up, C3 (at 1 kV), L-L & L-GND < 69 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to up...
GTIN:
6844127-80
,
Product code:
6844127-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 2
Connection between terminals L1–L2, L1–GND, L2–GND, L3–L4, L3–GND, L4–GND
Maximum operating voltage, Uc 28 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιimp, D1 test, (10/350μs), 4P 5 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 70 V
Up, C3 (at 1 kV), L-L & L-GND < 37 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to up...
GTIN:
6844125-80
,
Product code:
6844125-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 4 + GND
Number of protected pairs 2
Connection between terminals L1–L2, L1–GND, L2–GND, L3–L4, L3–GND, L4–GND
Maximum operating voltage, Uc 15 V
Maximum operating current, IL 1 A
Maximum signal frequency, F 30 MHz
Series line resistance (input – output), R 2 Ohms
Line capacitance (input – output), C 50 pF
Ιimp, D1 test, (10/350μs), 2P / 1P 2,5 kA / 1,25 kA
Ιimp, D1 test, (10/350μs), 4P 5 kA
Ιn, C2 test, (8/20μs), 2P / 1P 20 kA / 10 kA
Up, (at 5 kA), L-L & L-GND < 42 V
Up, C3 (at 1 kV), L-L & L-GND < 21 V
Main circuit GDT + TVS diode
Response time, tA 1 ns
Connection to network In line
Dimensions WxHxD (mm) 12x95x84,5 mm
Maximum conductor for terminal 0,75 – 4 mm2
Conductor terminals tightening torque 1 Nm
Housing material Thermoplastic V-0
Protection level of housing ΙΡ20
Operating temperature -40 oC ÷ +80 oC
Relative humidity 5% ÷ 95%
Rail mounting DIN-3 (TS-35/EN50022)
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device, suitable for the protection of electrical and electronic equipment, operating at low voltage digital and analogue signals. It is providing protection, to up...
GTIN:
6844126-80
,
Product code:
6844126-70
,
Customs tariff No.:
929.3.10.6
,
Gross weight: ,
PU:
1.00
Technical data
Protection type EN / IEC 61643-21 C1, C2, C3, D1
Number of poles 2 + GND
Number of protected pairs 1 (2 cables) + GND
Connection between terminals L1 – L2, L1 – GND, L2 – GND
Nominal operating voltage, Un 110 V DC
Maximum operating voltage, Uc 180 V DC
Maximum operating current, IL 0,6 A
Maximum signal frequency, F 250 MHz
Series line resistance (input – output), R 1,6–2,0 Ω
Line capacitance (input – output), C ≤ 20 pF (L–L) / ≤ 10 pF (L–G)
Ιn, D1 test, (10/350μs), Total 7,5 kA
Ιn, C2 test, (8/20μs), Total 20 kA
Up, (at 1 kV/μs – C3) < 250 V (L–L) / < 550 V (L–G)
Up, (at Ιn – C2) < 750 V (L–G)
Response time, tA 25 ns (L) / 100 ns (G)
Main circuit GDT + Diode block
Connection to network In line
Protection level of housing ΙΡ66
Dimensions WxHxD (mm) 93x93x62 mm
Operating temperature -25 oC ÷ +40 oC
Relative humidity 5% ÷ 95%
Maximum conductor for terminal 0,13 – 2,5 mm2 (L) / 0,2 – 2,5 mm2 wire, 0,25 – 1,5 mm2 ferrule (G)
Housing material Polycarbonate halogen free
Certification CE
Conformity with LVD 2014/35/EU
Installation only by qualified electrician IEC 60417–6182
ELEMKO management systems ISO 9001, ISO 14001, ISO 45001
Surge protective device providing primary and secondary overvoltage protection to Voice over Internet Protocol (VoIP) networks and devices connected to them. It is providing primary...
GTIN:
6803411-80
,
Product code:
6803411-70
,
Customs tariff No.:
929.3.10.5
,
Gross weight: ,
PU:
1.00